INTRODUCTION

Document Type: 
Collection: 
Document Number (FOIA) /ESDN (CREST): 
CIA-RDP85-00988R000100100140-6
Release Decision: 
RIFPUB
Original Classification: 
K
Document Page Count: 
12
Document Creation Date: 
December 16, 2016
Document Release Date: 
July 22, 2005
Sequence Number: 
140
Case Number: 
Content Type: 
MISC
File: 
AttachmentSize
PDF icon CIA-RDP85-00988R000100100140-6.pdf991.41 KB
Body: 
Unutea States Ap Jepeffdrl ot I ase 2005/08/02: 0 0100100140-6 COLY WITH 714?~~ GCY UN ~ Zia V. Off n TL)i ff 5 7 rul: 1: 7: (C M S Approved For Release 2005/08/02 : CIA-RDP85-00988R000100100140-6 What You Must Do With These Instructions if you are a Building Owner, Operator, or Manager with control over the building's heating, cooling, and hot water system, you must: ? Comply with these regula- tions, and ? Complete the appropriate forms. If you are a Building Tenant with control over any portion of the building's heating or cooling sys tem, you must: ? Comply with these regula- tions, and ? Forward these instructions to '-, the-bultding?'owner, operator, or manager. If you are a' Building Tenant with no control over any portion of the building's, heating or cooling sys-.,_ tem, you are requested to; Fo"Yard t1IC;.sc InotnUCtiO'i3 to the building owner, operator, . . or manager. The Emergency Building Temper- ature Restrictions Regulations,1 effective July 16, 1979, place tem- porary restrictions on temperatures for heating, cooling, and domestic hot water in commercial, indus- trial, government, and other non- residential buildings. The regula- tions generally require that thermostats be set no lower than 78?F for cooling, no higher than 65?F for heating, and no higher than 105? F for domestic hot water. Provisions are made, how- ever, for maintenance of room temperatures at these limits as an alternative to thermostat settings. The regulations also require room temperature set-backs during periods when the building is unoccupied. Owners and operators of build- ings covered by the regulations are required to post a Certificate of Building Compliance in a prominent location in their build- ings within 30 days of the effec- tive date of the regulations. Tenants also are required to com- ply with the regulations although they are not required to post a Certificate or file documents with the Government. Certain types of buildings and portions of certain buildings are excluded from the temperature restrictions. Exemptions also are available under-certain specified. conditions. Civil penalties of up to $5,000 and criminal penalties of up to $10.000 are provided for violations of the regulations. The regulations ti,,wW rernaln in effect until April 16, 1 Pursuant to Sections 201(a) and (b) of the Energy Policy and Conservation Act of 1975 (42 US. C. 6201 et. seq.), the President developed Standby Conservation Plan No. 2, Emergency Building Temperature Restrictions (the Plan) and sent it to the Congress on March 1, 1979. The Department of Energy (DOE) published a notice in the Federal Register on March d. 1979 (44 FR 12906), of the President's adoption of the Plan. The Plan was approved by resolutions of the Senate on May 2, 1979, and of the house of Representatives on May 10, 1979. Proposed regulations were published in the Federal Register on June 1, 1979 (44 FR 31922). DOE published final regulations in the Federal Register on July 5, 1979 (44 FR 39354). On July 10, 1979, the President issued and trans- mitted to Congress a Proclamation srating his finding that a 'severe energy , u:-p;. roue ruption ... currently exists with respect to the supply of imported crude oil aria l.=ro;eeum products" (44 FR 40629). In the Prcc~'rmation, the President invoked his autho''ty to Imple- ment the emergency building temperature restrictions, and declared July 16, 1979, as the effective date of the Plan and the regulations. DOE published a notice in the Federal Register on July 16, 1979, of the effective date of the Plan and the regulations (44 FR 41205). Approved For Release 2005/08/02 : CIA-RDP85-00988R000100100140-6 /08/02: CIA-RDP85-0098814Q90100100140-6 Part A: How to Determine if the Regulations Apply to Your Building in Buildings which are covered. The regulations cover all non- residential buildings in the coun- try, unless a building is specifi- cally excluded or exempted. 2^ Buildings which are ex- cluded. The regulations exclude all or portions of four types of buildings: ?Residential Buildings. Build- ings, or areas of buildings, used exclusively for residential pur- poses are not subject to these Cm Hospitals and Other Health- Care Facilities. Facilities autho- rized under State law to provide hospital or health-care services (e.g., general or specialized hos- pitals, clinics, and nursing or con? valescent homes) are excluded. However, if the administrative or other portions of such buildings where patient care is not provided have separate heating, cooling or water temperature controls, such areas are covered by the regula- tions. Medical, dental and nursing school buildings, administrative buildings,. and other buildings, ? associated with hospitals and other health-care facilities, but where patients are not treated, are covered and must comply with the regulations. The offices of temperature restrictions ,. However, ;-physicians and dentistsare not..- ' non-residential portions of such buildings that have separate -heating, cooling or hot water - temperature controls, and which 'trial or other business purposes '...are covered and, must- comply with the regulations. w 'Hotels' and Other Lodging.. Facilities. Buildings that, in the ordinary course of business, pro- vide lodging or sleeping accomo- dations to the public or to private guests are not covered by these regulations. However, if the non- sleeping areas of such buildings have separate heating, cooling or water temperature controls, these areas are covered by the regula- tions. In hotel buildings, for example, the retail stores, restau- rants, meeting rooms, lobbies, and offices that have separate temperature controls are covered and must be in compliance with the regulations. excluded, but an exemption for health-related reasons is avail- able: (For further. detail, ' please see the Exemption Information Form.) Elernientary Schools, i' uu c3iy Schools, and Day-Care Centers. Buildings housing elementary . schools (through. sixth grade), ' . nursery 'schools, and day-care centers (as defined by State or - local law) are not covered by the regulations. However, if a building is used by both elementary and junior or senior high school level students, and those areas used by junior or senior high school students have separate heating, cooling or water temperature con- trols, then those areas are covered and must be in compliance with the regulations. It is possible for portions of a building to be excluded while the remainder of the same building is covered by these regulations. If you determine, after careful read- ing of these instructions, that your entire building comes under one of the exclusions, you need do nothing further. However, if you determine that your building is not wholly excluded, you must comply with the regulations. 4EN ^ Buildings and facilities which are exempted. A building owner, operator or tenant may be entitled to an exemption from the temperature restrictions under certain specified conditions. These exemptions are described on the Exemption Information Form. The exemptions are of two types: (1) general exemptions, which relate to the circumstances 'of a business activity, and (2) system related exemptions, which relate to conditions or operating features of heating, cooling or hot water equipment :...arid` systems. As a rule, the general exemp- tions are available only to that portion or area of a building where the specified conditions .exist For example, an exemption for "special equipment," such as a computer facility. would be available only in those areas with- in the covered building containing such equipment, and in no other areas: Only if the building is served by a single master temperature control does the exemption ex- tend beyond such areas. Approved For Release 2005/08/02 : CIA-RDP85-00988R000100100140-6 Such support documentation should be retained by the owner/ operator, along with the Form, and must be available for review in the event of an inspection of the building. Part C: How to Comply with the Regulations -Adjusting Air Temperatures Part B: How to Comply with the Regulations - Certificates and Forms This manual contains three separate forms: (1) Certificate of Building Compliance, (2) Exemp- tion Information Form, and (3) Building Compliance Information Form. Only the owner or operator of the covered building is required to complete these forms. Instruc- tions on the responsibilities and liabilities of tenants are presented in Part E, below, Certificate of Building Com- pliance: In all cases (unless the building is wholly excluded), the owner or operator must complete this form, remove it from the manual, and post it in a prominent public location within the building, lobby or bulletin board.. Failure to post this Certificate by August 15, 1979, 30 days after the effective `date of the regulations, is a violation subject to penalties. However, delays occurring in the distribution and receipt of the forms will be taken into account in determining compliance with the certification requirement. exemption Information Form- his? form is to be completed only if one or more of the specified exemptions are claimed for areas within a covered building, or if a special exception has been granted by DOE. If exemptions are claimed by tenants of the building, the building owner or operator is advised to obtain a written statement from such tenants which describes and justi- fies the claimed exemption(s). In Heating and Cooling Tem- perature Restrictions. The regu- lations divide heating, ventilating, quired to apply to DOE for an and exemption from these temperature air-conditioning (HVAC) sys- restrictions. Any authorized terns into two basic categories: specified on the (1) simple systems which, at any exemption (as given Exemption Information Form) time, can either heat or becomes effective immediately cool, but cannot heat and cool upon your completion of the simultaneously, and (2) compound m. You may be subject to a or integrated systems which have For the capability penalty, however, if a claimed to heat and cool exemption.is determined to be simultaneously, or heat one area invalid upon a later inspection and of a building While cooling another. ruling by DOE. A building owner or operator shall not be liable for These instructions cover those penalties as a result of an invalid periods when the building is nor- exemption claimed by a tenant, malty occupied. A building is con sidered occupied, day or night, Building Compliance information when alt of part of it is used for ordinary or customary functions Form: Submittal of this form is mandatory only if claiming 'an exemption. Those claiming an but.not,including such daily service functions as cleaning and. maintenance. Instructions for exemption must complete the heating and cooling during un- Form and return it'to DOE with occupied periods are provided droner postage by-August 15, - -. below. 1979, or within 10 days after receipt of this manual, whichever aSimple Systems:. When the cooling system Is operating, the - thermostats shall be set so that no cooling energy is used to lower the room temperature below 78? F. When the heating system is operating, thermostats shall be set so that no heating energy is used to raise the room temperature above 65?F. (The temperature is to be measured with a "dry-bulb," or ordinary thermometer.) How- ever, when cooling, the dry-bulb temperature may be lowered below 78?F to the extent neces- sary to lower the room "dew- point" temperature to not lower Approved For Release 2005/08/02 : CIA-RDP85-00988R000100100140-6 08/02 : CIA-RDP85-00988RQ00100100140-6 than 65?F. (Dew-point temperature is a measure of humidity. Instruc- tions on how to determine the dew-point temperature are pro- vided below under Temperature Measurement Techniques.) You may comply with these re- quirements by simply setting the thermostat(s) to the required point, i.e., 78? F when cooling or 65? F when heating, or you may comply by adjusting the thermostat(s) so that the room air temperature is maintained at the prescribed levels. For further instructions, see Temperature Measurement Techniques, below. e Compound or Integrated Systems: These systems include dual-duct, reheat, recool, multi- *'one`fans,.fan-coit'Units in dorn- bination with central air or refrig- erant,-induction units in combina-. tion with central air, central systems with independent window air-cortditioners_or heat pumps, and similar systems. Several alter- natives are provided for compli- ance in buildings with these systems, depending upon the type or configuration.of HVAC 1. The building owner/operator may set each temperature control device so the dry-bulb temper- ature (as measured in any room controlled by the same device) is not lower than 78?F when cooling or higher than 65? F when heating. For example, if the air temper- ature in three separate rooms is controlled by one thermostat, you may use the measured dry-bulb temperature in any one of those rooms to determine whether you tre in compliance with the regula- tions, regardless of the thermostat setting. This same approach may be applied to control the dew- point temperature. 2. Alternatively, the owner! operator may use one of the com- pliance strategies outlined below: a. Heating coils combined with constant-air-volume and/or variable-air-volume HVAC sys- tems. In such systems, the heating coils used for exterior zones of a building typically are located in fan-coil units, induction units, baseboard heaters or similar units. To be in compliance, you may set the air-temperature con- trol devices so that: ? When cooling, no heat is pro- vided to the heating unit; ? At all times, no coolant liquid e.g., chilled water or refriger- ant,.is supplied to the cooling colts at temperatures tielbw, .:When heating, the room:dry- bulb temperature is maintained not higher than 65? F. C. Constant or variable-air- volume-with-reheat and variable- air-volume ("all-air') systems: To be in compliance, set air temper- ature control devices so that: ? At all times, the temperature of the air leaving the cooling coils is at least 60'F; and ? When cooling, the heating system is turned OFF and the thermostats (or other local temperature control devices) are set at 78'F; and ? When heating, the cooling system is turned OFF and the thermostats are set at 65? F. 3. Instead of using any of the above compliance strategies, the ownerlopera#or may use.an alter- native approach if a licensed pro- fessional engineer certifies it will consume less energy for heating and -cooling the building than the approaches described above. How- such an alternative approach must include adjusting the cooling 0. Central ChIller"heat PL;.-,,p HVAC systems. Sucn systems typically use a central chiller to .supply cookair to the inner core.',. of the building and circulate the warm condenser water from the chiller to the exterior rooms where heat is extracted by room heat pumps. For such systems, the building shall not be cooled below 78? F. When heating, the exterior zones shall not be heated above 65?F. systenl so that: (a) no i;qulu coolant is provided to cooling coils at a temperature below .55? F`; or(b)-the dry-bulb . temperature of-air leaving the cooling coils is 60?F or higher. Important Note: You may alter- nate at any time between the compliance strategies described in B-1, B-2, and B-3, above, to achieve permissible temperature levels. For example, with a fan- coil system, if room temperature when cooling cannot be reduced to 78? F with a circulated chilled water temperature of 55--F, you may lower the temperature of the chilled water. In doing :;o, how- ever, you must then insure that room air temperature is not lowered below 78?F. If at another time, outside air temperatures or Approved For Release 2005/08/02 : CIA-RDP85-00988R000100100140-6 Approved For ease 2005/08/02 : CIA-RDP85-00988RQWO100100140-6 interior heat loads should be reduced, you may adopt the alter- native approach of maintaining chilled water at 55? F, or higher, regardless of the actual room air temperatures. Other actions may improve levels of comfort. Fans will assist the normal movement of air. Windows may be better in- sulated with shades or drapes. People may be moved away from hot or cold exterior walls and windows. 2 When a Building Is Unoccupied. These provisions apply to all covered buildings, whether they have simple or complex HVAC HVAC systems must be turned OFF when a building is to be unoccupied for 8 hours or more,. unless damage would occur to the building or its contents or the 'minimum anticipated outdoor air temperature (dry-bulb) during the unoccupied period Is expec:tod to be lower than 50?F. In the latter case, the temper- :aturwcontrol devices must be set. so that either. (a) the room dry- bulb temperature is not greater than 55? F, or (b) the heated supply-air dry-bulb temperature is less than 100?F, or (c) the heating- water temperature is less than 120? F, or (d) the room air temper- ature control devices are set to a level not higher than 55? F, or at their lowest set-point. Both heating and cooling systems may be turned OFF by turning off the circulating air or circulating water systems. 3 v Temperature Measurement Techniques. To determine whether a building is in compliance with these temperature restrictions, any one of the following measurement techniques may be used: AsCornpliance may be shown by reading the set-point of the thermostat. Building owners/ operators are required to maintain thermostats at reasonable toler- ances of accuracy. Any intentional alteration or damaging of such devices to produce inaccurate readings is a violation of the regulations. - Inference from the dew- point or from wet-bulb and dry-bulb temperature mea- surements (psychrometer). ? For measuring wet-bulb temperature: - An instrument for measuring wet-bulb temperature (psy- chrometer); or - Inference from the dew- point temperature or relative humidity. Dew-point or wet-bulb temper- atures. and relative humidity may be measured within two feet of the humidity space-conditioning control device (humidistat), if located in the room, or in the same location used in measuring ,tho:dry-bulb temperature. To allow. a Alternatively, measurements for HVAC system cycling, several temperature.and humidity readings of the actual room temperature and humidity. 'levels may be made' by the following means: ?? For.,measuring dry-bulb ;- temperatures: h,rmomc Ler may be spaced. to accommodate the time needed for compressors to gq.through their "on-off" .,cycles, Where an air-temperature control device controls the tem- pe ature in more than one r ;o ^, placed within two feet of the the measurement(s) may be made thermostat; .or in any one room controlled by Averaging the..therrnometer . ttiat. Ievice.; , :. feadings taken two feet away from and at the center of each external wall in the room, and at the center of the room; or - Taking the temperature at the center of the room if there are no external walls. ? For measuring dew-point temperature: - Using an instrument that indicates dew-point temper- ature; or - Inference from the dry-bulb temperature and relative humidity (See Table 1 below.) ? For measuring relative humidity: - A humidity-indicating device (hygrometer); or .Ar o Use of Portable Heaters and Ventilating Equipment. The use of auxiliary heating devices, e.g., portable electric heaters or heat lamps, is prohibited, except: (1) when the room dry-bulb tem- perature is below 65? F, or (2) to provide spot heating when the building is unoccupied. For example, a person working over- time may use auxiliary heating equipment. The use of ventilating f,^s or ventilating systems is even when such use will r,-. se the room temperature above 6'5.? F (dry-bulb) or lower it below 78? F (dry-bulb). The use of free-standing fans within rooms is authorized at all times. Approved For Release 2005/08/02 : CIA-RDP85-00988R000100100140-6 s Temperature Restrictions U11 I LAZ 0 N_- - S Table 1: Dew-point temperature (?F) estimated from measurements of dry-bulb temperature and relative humidity. Dry-Bulb Temperature Relative Humidity (Percent) 70 51? 56? 60? 64? 67? 75 55? 60? 65? 68? 720 78 580 63? :.6T 710..: .750 80 600 650 690 730 770 ,..:: .85 78? 82?; and a relative humidity gauge, the approximate dew-point temper ature can be estimated from this Table. Example: If the indoor -dry--bulb temperature measures 78?F and the relative humidity (measured within the room) is 70 percent,, the dew-point temper- ature Isappr6x1mat6ly 67? F. Under these conditions, the thermostat maybe Iowered below 78?F to reduce the dew-point Part D: How to Comply with the Regulations - Adjusting Water Temperatures These restrictions apply only to "domestic" hot water- that is, water used for personal hygiene or general cleaning, for example, in rest rooms or janitorial facilities. Temperature control devices for domestic hot :rater must be set at 105? F or the lowest setting on the control device, whichever is higher. When a building is unoccu- pied for more than eight hours, the domestic hot-water cir- culating system pumps (if any) must be turned OFF, unless this would damage the building, its systems, or its internal processes. Tenants of buildings covered by these regulations who have con- trol of temperature control devices such as wall thermostats and win- dow air-conditioners are required to maintaFn such devices at the levels required by the regulations. temperature to not more than Failure to comply with these 65oF.:This may be`done by first requirements is a violation subject lowering the thermostat one to penalties. ..degree to 770F, and rechecking A tenant entitled to an exemp- the relative humidity after the lion is required to notify the groom temperature has stabilized. If the estimated dew-point temperature is still above 65?F, the thermostat may be lowered. slightly'agairy, and this process repeated until the estimated dew- point'is 65?F. Exemptions from these require- ments are described on the Exemption Information Form. Compliance with the hot-water temperature restrictions may be determined by measuring the water temperature: a in the hot-water supply line; b. at the tank temperature con- trol point; or c. at the tap nearest to the tank discharge point. Some systems may not have large hot-water storage capacity. In such cases, operators may take advantage of option "c" by install- ing a mixing valve between the building owner or operator in writing of such exemption. Tne exemption becomes effective upon notification of the owner/ -operator: The.owrier/operator will. attach the claimed exemption to the Exemption Information Forme which he is required to complete and retain on file. Part F: Special Exceptions In addition to the exemptions (see the Exemption Information Form), special exceptions will be granted when these regulations create special hardship, inequity, or an unfair distribution of the burden. Applications for special excep- tions must be in writing and signed by the person or persons so affected. The application should set forth the revelant facts and ex- plain why these regulations create a special hardship, inequity, or an unfair distribution of the burden. The building (or area therein) in which the requested exception would apply also should be identified. Approved For Release 2005/08/02 : CIA-RDP85-00988R000100100140-6 hot-water tank and the nearest tap. This will allow water in the storage tank to be heated above 105? F. Water temperature control devices must be maintained within reasonable tolerances of accuracy, and any alteration with the intent of having that device function in- accurately is prohibited. Part E: Tenant Responsibilities Approved For Release 2005/0./02 CIA-RDP85-00988R000100100140-6 EME3ENCY BUILDING. TEMPERATURE RESTRICT CERTIFICATE OF BUILDING COMPLIANCE Building Name Address This is to certify that the undersigned is in compliance with the Emejency Building'Temperature restrictions Plan;:Accordingly, the cooling, heating, and hot water temperatures of these premises have been adjusted in an attempt tci-achieve the reductions in energy consumption contemplated under the emergency measures. ONS No. of Stories . No. of Square Ft- El Full Compliance (Check Appropriate Category) ^ Exempted Compliance (See Building Manager for Exemption Details) ^ Excepted From Compliance (See Building Manager for Exception Application) B iilding Owner or Operator Date Signature Approved For Release 2005/08/02: CIA-RDP85-00988000100100140-6 Approved For 00140-6 Building owners or operators must complete this form and keep it on file. Please do not forward the form to the Department of Energy. 1. Respondent/Building Identification 2. Building Owner Identification (If different) 3. Building Type (Please Check One) ^ C. restaurant ^ D. retail store (other than retail food store). S ; ::r:. ^ A. industriallmanufacturing ^ B. school ^ F. office ''^ G."hotei/lodging ^ H. shopping center ^ I. warehouse "^ J. retail food store ^ A. Maintenance of specified temperature levels is required by manufacturer's warranty (or other applicable instructions or equipment service con- tracts) to prevent damage to special equipment. 490.31(a)(1) Example: computer rooms. ^ B. Maintenance of specified temperature and humidity levels is critical to materials and equip- ment used in manufacturing, industrial or com- mercial processes. 490.31(a)(2) Examples: freeze drying, certain printing processes, and manu- facturing and handling of explosives. General exemptions (490.31) vide necessary temperatures to exempt areas. Exemptions shall become effective when claimed. There are two types of exemptions: (1) a general exemption which results from. a situation of-.your 4.'Exemption Information. 'Instructions. You are entitled to claim'exernption'for~ as much of the building's area as is required to pro- C. Maintenance of specified temperature and humidity levels is required for proper storage or handling of food or other agricultural commod- ities, raw materials, goods in process, and finished goods. 490.31(a)(3) Example: perishable- food warehouses. ^ K. combination of above (please specify letters) ^ L other (please specify) business,, and `(2) a system-specific exemption due to the nature of your building's heating and cooling and/or hot water systems. Please check the exemp- tion(s) that apply to your building. Note that section numbers refer to Department of. Energy regulations . (44`FR 39354; ;)uly 5,1979). ^ D. Special environmental conditions are required to protect plant or animal life or materials essen- tial to the operation of a business. 490.31(a)(4) Examples: greenhouses, museums, certain laboratories, art galleries, zoos, and veterinary hospitals. ^ E. Maintenance of specific temperature levels is required to protect the health of persons 490.31 (a)(5): (i) in offices of physicians, dentists, and other members of health care professions licensed by the state to provide health-related serviocs: or (ii) engaged in rehabilitative physical therai-'y in physical therapy facilities; or (iii) utilizing indoor swimming pools. (This exemption applies only to heating restrictions.) ^ F. Maintenance of specific temperature or humidity levels is required to prevent damage to the structure or insulation of the building. 490.31 (a)(6) Approved For Release 2005/08/02 : CIA-RDP85-00988R000100100140-6 Approved For +ease 2005/08/02 : CIA-RDP85-00988FW0100100140-6 necessary for the temperature to reach the mini- mum level otherwise permitted during the build- ing's occupied period. 490.18(b) ^ L. If a licensed Professional Engineer (P.E.) certi- fies that operation of the HVAC system in accor- dance with the regulations will result in con- sumption of more energy than will some alternate procedure and the ownerloperator agrees to implement this alternate procedure. 490.12(e)(1) Exemptions affecting hot water systems (490.24) ^ M. Buildings where the domestic hot water heat- ing equipment also provides hot water for manu- facturing, industrial or commercial processes which require hot water temperature higher than '105?F. 490.24(a) ^ N. Buildings where domestic hot water is the only source of water available for dishwashing or other purposes which are covered under state or .local health regulations prescribing .a higher rn.Infmuin'terriperature'?than` 105? 1=. 490.24(b) ,0. Buildings. where domestic. water heating!. space heating boilers are combined. (This :.i`s, uSed.):490.24(c). ElP, Buildings where solar?nPrgy (axcapt for pumps and fans) provides the only source for domestic hot water heating energy. When a non- solar energy source Is operating together with -solar energy, this exemption does not apply. 490.24(d) ^ 0. Buildings where otherwise wasted energy provides the only source for domestic hot water heating energy. (Applies only at those times when wasted energy is the only source of energy.) 490.24(e) 6. Specific Exceptions ^ Check here if a specific exception has been granted by the Department of Energy for the building or any portion of the building. System-specific exemptions (490.18) Exemptions affecting heating and cooling systems (4-0.18) El G. Buildings or portions thereof which are neither heated nor cooled; and buildings or portions thereof which are equipped with space heating devices and space cooling devices with total rated output less than 3.5 Btu per hour (1 watt) per square foot of gross floor area. (You should be able to find the output on a !abet on the equipment, in the manufacturer's literature, or in the warranty statement.) 490.18(a)(1) ^ H. Buildings that are cooled by a heating, venti- lating, and air conditioning (HVAC) system capable of using outdoor air or evaporation of water for cooling effect without operation of a vapor compression or absorption-refrigeration system. {Applicable only at those times when such a system is used for cooling and when the ;outdoor air and/or evaporator effect provides the. onfy cooling``source:)'490.18(a)(2) ` ''' ^.1. Buildings that use otherwise wasted energy in, or to power, HVAC systems. (Applicable only at, those times when wasted energy is the only -enitrra of hnatinn nnri cnniinn nnnrnvl . ^ J. Buildings that use solar HVAC systems. (Applicable only at those times, when solar ? :energy i$ the only source, of heating and cooling:. K:' E1uildings that have HVAC'systems whose capacity is insufficient to maintain the building at minimum authorized temperature or humidity levels for cooling. The reduced temperature levels may be maintained only for the period 5. Exemption Justification ^h exemption checked in Section 4 above, n hereto, and retain for possible inspection, -n statements provided to you by tenants claim- 4:.,; ., enptions within your building. Approved For Release 2005/08/02 : CIA-RDP85-00988R000100100140-6 Approved BUQWRT kD NO ORN t*4 MOQM0-6 r.ri. (Submittal of this Form is Mandatory if any Exemptions are Claimed.) Please Type or Print-See Instructions on Pages 3. t twilding Owner-Operator-Manager ,,j 5 rvet Address :;uilding Type (Please Check One). k industrial/ Manufacturing B. School ..?.' C. Restaurant C:. H6'tel1Other-L6d6ing - ' D. Retail Store (other than retail food store) E Hospital/Health Care F. Office Exemptions (If Claimed).'., . A.._Equiprnent Warran B. Processes C. Perishables.. O. Plant/Animal/Materials E. Health. Protection ^ H. Outside Air G. No System ^ I. Waste Energy d J. Solar Energy ^. K. Under. Capacity ^ L. Certification F. Action Taken A. Full Compliance ^ B. Compliance With Authorized Exemptions or This Building Was Originally Constructed ,.5 of Fuels Used For Heating and Air Conditioning Heating :ctricity r lateral Gas f:. Fuel Oil 0. Coal F F. Propane E. Other (specify) 2. Building Size A. Approximate Gross Floor Area in ^^^^ Thousands of Square Feet B. Number of Stories Heated and/or Air Conditioned ^^^ ^ H. Shopping Center ^ I. Warehouse ^ -J: Retail Food Store ^ K. Combinations of Above (insert letters) ^ L. Other (please use less than 15 letters) ^ N. Dishwashing ^.0. Combined Solar Energy .': .. ^ Q. Waste Energy ^ C. Exception Requested Air Conditioning ^ A. Electricity ^ B. Gas ^ C. Other (specify) D. What percentage of this building's gross floor space is air conditioned? ^^^ '10 Approved For Release 2005/08/02 : CIA-RDP85-00988R000100100140-6 The letter, and any supporting documents, should be sent to the ~a DOE Regional Offices. Addi- the following Department of nearest DOE Regional Office of tional program information and Energy Regional Offices. Hearings and Appeals. The materials may be obtained from envelope should be labeled: "APPLICATION FOR EXCEPTION- EBTR." Mailing addresses for the Region 1 Connecticut, Massachusetts, five DOE Regional Offices of 150 Causeway St. Maine, New Hampshire, Rhode Hearings and Appeals are: Boston, MA 02114 Island, Vermont 26 Federal Plaza (617) 223-3106 New York City NY 10007 , Region II New Jersey, New York, Puerto 1655 Peachtree Street, N.E. 26 Federal Plaza Rico, Virgin Islands Atlanta, GA 30309 New York, NY 10007 (212) 264-8856 2626 Mockingbird Lane Dallas TX 75235 , Region III Delaware, District of Columbia, 175 West Jackson Street 1421 Cherry St. Maryland, Pennsylvania, Virginia, Chicago, IL 60604 Philadelphia, PA 19102 West Virginia (215) 597-3606 111 Pine Street . San Francisco CA-'94:111" , Region IV Alabama, Canal Zone, Florida, 1655 Peachtree St. N.E Mississippi Georgia Kentucky Important Note: a special excep- , . , , , Atlanta GA 30309 Carolina, South Carolina North tion does not become effective , _ , (404) 881-2838 Tennessee until such time as it is granted by the Department of Energy and the Region V Illinois,. Indiana, Michigan, 175 W. Jackson St. :Minnesota, Ohio, Wisconsin Part G; Obtaining Further information ' r. ?.._ 6o Toll-Free Telephone Lines. Information concerning this pro- gram and how to comply with its regulations may be obtained by using the toll-free telephone numbers listed below. The lines will be operational between 9:00 A.M. and 5:30 P.M. (Eastern time), Monday through Friday. , Region VI 2626 W. Mockingbird Lane P.O_ Box 35228 - . . Dallas, TX 75235 (214) 767-7777 Arksisas;;Okiahoma,?Louisiana, New Mexico, Texas Region VII 324 East 11 St. Kansas City, MO 64106 (816) 374-3815 Iowa, Kansas, Missouri, Nebraska Region VIII . . .. , .. Colorado, Montana, North Dakota, Continental U.S.: 800-424-9122 1075 S. Yukon P.O. Box 26247, Belmar Branch Lakewood, CO 80226 (303) 234-2765 Alaska, Hawaii, l-uerto Rico, Virgin Islands: 800-424-9088 1 Region IX Metropolitan 1 1 111 Pine St. San Francisco, CA 94111 Washington, D.C.: 252-4950 (415)556-7148 Region X 915 Second Ave. Seattle, WA 98174 (206) 442-7285 South Dakota, Wyoming, Utah American Samoa, Arizona, California, Guam, Hamvaii, Nevada, Trust Territories of the Pacific Alaska, Idaho, Oregon, Washington Approved For Release 2005/08/02 : CIA-RDP85-00988R000100100140-6