NORTH KOREAN ELECTRIC POWER DAMAGE ASSESSMENT REPORT
Document Type:
Collection:
Document Number (FOIA) /ESDN (CREST):
CIA-RDP78T05694A000300010025-8
Release Decision:
RIPPUB
Original Classification:
S
Document Page Count:
14
Document Creation Date:
December 28, 2016
Document Release Date:
June 7, 2001
Sequence Number:
25
Case Number:
Publication Date:
August 20, 1956
Content Type:
IM
File:
Attachment | Size |
---|---|
CIA-RDP78T05694A000300010025-8.pdf | 452.86 KB |
Body:
JOB NO.
Approved For Release 200141iEtERRADP78T
CONFIDENTIAL
COPY No.
PHOTOGRAPHIC INTELLIGENCE MEMORANDUM
NORTH KOREAN ELECTRIC POJ
KTT.
BOX NO.
FOLDER NO.
TOTAL ROCS fiEREIN
GE ASSESSMENT REPORT
Declass Review by
NIMA/DOD
op/I - 204
20 August 1956
LIBRIkiel
master nes
DOCUMEN'i Nt')
NO CHANGE': It AS,. I-
DECLa
CLASS CHAN(' i'E) TO: TS
NEXT REVIEW CATE:
AUTH: HR
D,AE: REVIEWER:
CENTRAL INTELLIGENCE AGENCY
OFFICE OF RESEARCH AND REPORTS
CONFIDENTIAL
Approved For Release 2001/08/13 : CIA-RDP78T05694A000300010025-8
SECRE7*-
c-i
Approved For Release 2001/a/AROMDP78T05694A000300010025-8
WARNING
This material contains information affecting
the National Defense of the United States
within the meaning of the espionage laws,
Title 18, USC, Secs. 793 and 794, the trans-
mission or revelation of which in any manner
to an unauthorized person is prohibited by law.
SED
Approved For Release 2001/08/13 : CIA-RDP78T05694A000300010025-8
Approved For Release 2001/08$16WIMP78T05.6Q4151101q010/A8L
CON.
NORTH KOREAN ELECTRIC POWER DAMAGE ASSESS!-'ENT REPORT
This study presents an estimate of bomb damage suffered by
electric power facilities in North Korea based upon analyses
of aerial photography. Important installations not covered in
this report will be subject to supplementary reports that will
be issued as additional photography becomes available.
This report does not necessarily indicate the condition of
the installation at the cessation of hostilities, as some of the
photography was taken as early as The dates of aerial
coverage are presented with the dama7e estimate for each electric
power installation.
DENT LAL
Approved For Release 2001/08/13 : CIA-RDP78T05694A000300010025-8
?SECRET-
25X1D
Approved For Release 2001/066CREEP78T05694A000300010025-8
HYDROELECTRIC POWER PLANTS
25X1D
CHOSIN #1 (H-1)*
(e)
(b)
(c)
Four of 4 penstocks broken
Approxinately one-third of generator
house collapsed
Sub-station destroyed
UTM
Coordinates
CV551528
CHOSIN #2 (11-2) cv573474
(a) Roof off surge tanks; tank empty.
(b) Four of 4 penstocks broken
(c) Generator hall pierced in several
places
(d) Sub-station destroyed
(e) Auxiliary intake destroyed
CHOSIN #3 (H-3) CV584431
(a) Roof off surge tank
(b) Three of 3 penstocks broken
(c) Genergtor hall pierced by bombs
in several places
(d) Sub-station destroyed
(e) Auxiliary intake pierced by bombs
in one place
CHOSIN #4 (H-4) CV646334
(a) Roof off surge tank and tank empty
(b) One of 3 penstocks broken
(c) Overflow pipe broken
(d) Sub-station destroyed
FUNEI #1 (H-5) EBS10564
No aoparent damage (poor coverage)
FUNEI #2 (H-16) EB558562
(a) Penstock intact
(b) Generator house appears intact
(c) Sub-station destroyed
(d) Ten of 15 nearby buildings destroyed
*H-1, etc. indicates the location of installation on attached map
Approved For Release 2001/08/13 : CIA-RDP78T05694A000300010025-8
SECRET
Approved For Release 2001/061datEITDP78T05694A000300010025-8
25X1D
UTM
Coordinates
FUSEN #1 (H-7) CV779671
(a) Two of 4 penstocks broken
(b) Roof off generator house
(c) Sub-station destroyed
FUSEN #2 (H-8) cv8o5621
(a) Penstocks intact
(b) Ends and roof off generator house
(c) Sub-station damaged
FUSEN #3 (H-9) CV802561
(a) Penstocks probably broken
(b) Three-quarters of generator house
destroyed
(c) Sub-station destroyed
FUSEN #4 (H-10) cv766504
(a) Roof off surge tank
(b) Penstocks underground
(c) Roof and one end off generator
house due to one direct hit on
end of building
(d) Sub-station destroyed
KONGSAN #3 (H-11) DT015982
(a) Generator building partially gutted
(b) Transformer yard destroyed
(c) Penstock ruptured
KONGSAN #4 (H-12) DU030010
(a) Generator building completely gutted
(b) Penstock ruptured
(c) Half of surge tank roof missing
(d) Transformer yard damaged
2
Approved For Release 2001/08/13 : CIA-RDP78T05694A000300010025-8
SECRET
Approved For Release 2001/060CREIFDP78T05694A000300010025-8
KYOSEN #1 (H-13)
(a) Six to 8 of 8 penstocks broken
(b) Generator house pierced in 3 places
(c) Sub-station east of generator house
destroyed; sub-station on northwest corner
of generator house partially destroyed in
spite of heavy revetments. Four trans-
formers appear intact
(d) Dam adjacent to generator hall intact
(e) Auxiliary intake broken in one place
(f) Exhaust tunnel pierced in one place
KYOSEN #2 (H-14)
(a) Surge tank roof off
(b) Three of 4 penstocks severed
(c) Generator hall three-quarters demolished
(d) Transformer yard heavily damaged
KYOSEN
#3 (i1-15)
Roof off surge tank and tank breached
Water flowing freely from side of hill
below surge tank due to ruptured
underground pipe
Afterbay covered by alluvial material
which was deposited when surge tank
was brerched
Three or 4 of 4 penstocks broken
Overflow pipe broken
Generator house roof half off; remainder
of roof pierced in several places
Sub-station destroyed
Exhaust tunnel pierced in several places
KYOSEN #4 (11-16)
(a) Roof off surge tank
(b) Two cr 3 of 4 penstocks broken
(c) Roof off most of generator house
(d) Generators probably covered with earth
(e) Sub-station destroyed
(f) Several transformers revetted near
generator house
UTM
Coordinates
?DA53414o
DA670028
DV776953
DV867826
3
Approved For Release 2001/08/13 : CIA-RDP78T05694A000300010025-8
SECRET
25X1D
25X1D
25X1D
25X1D
Approved For Release 2001/06F2CEIEXDP78T05694A000300010025-8
25X1D
SERYUCHON POWER PLANT AND DAM (H-17)
(a) Only the power plant was bombed
(b) No apparent damage to generator house
25X113 (c)
SUIHO (H-18)
(a) Generator hall has large hole in
roof at south end, plus 3 smaller
holes
(b) Transformer yard nearly completely destroyed
(c) Adjacent buildings destroyed
(d) Adjacent hillside railroad line severed
UTM
Coordinates
CU378814
xE664800
4
Approved For Release 2001/08/13 : CIA-RDP78T05694A000300010025-8
SECRET
Approved For Release 2001/08515CagITDP78T05694A000300010025-8
THERMAL :ELECTRIC POWER PLANTS
25X1D
UTM
Coordinates
HOERYONG (T-1)* EB6298
(a) Generator and boiler house destroyed
(b) Transformer yard intact
KILCHU (T-2) EA2734
(a) Generator and boiler house roof
destroyed, walls caved in, interior
totally gutted
(b) Transformer yard heavily damaged
KYOMIPO (T-3) YC290910
(a) Generator and boiler house roof
heavily damaged and pierced
(b) Transformer yard heavily damaged
SINUIJU (T-4) XE1839
(a) Generator building gutted
(b) Transformer station building gutted
(c) Cooling ponds intact
(d) Heat pipes to adjacent plant destroyed
*T-1, etc. indicates the location of instanation on attached map
Approved For Release 2001/08/13 : CIA-RDP78T05694A000300010025-8
SECRET
Approved For Release 2001/08FECREOP78T05694A000300010025-8
SUB-STATIONS
CHANGHUNG -NI (S-1)*
Transformer yard destroyed; control house
Intact;. 3 of 4 revetted transformers on
hillside
UTM
Coordinates
pv656485
CHIDOK (S.2) EA169073
No damage
CHONGJIN #1 (S-3) E13661280
Transformer yard and control house
destroyed; 3 revetted transformers
nearby
CHONGJIN #2 (8-4) EB666252
(IRON INDUSTRY SUB-STATION)
Transformer yard and control house
damaged; 6 revetted transformers nearby
CHONGJIN #3 (S-5) EB658277
Transformer yard damaged; control house
intact; 3 transformers revetted nearby
CHONGJIN #4 (5-6) EB640248
Transformer yard damaged; control house
intact; station possibly still in operation
CBUURONJANG (5-7) EB504036
No damage to station; 5 transformers
revetted nearby
HAGARU-RI (5-8)
Transformer yard damaged; control house
intact; 3 or 4 transformers revetted
on hillside
*5-1, etc. indicates the location of installation on attached map
Approved For Release 2001/08/13 : CIA-RDP78T05694A000300010025-8
SECRET
CV519715
25X1D
Approved For Release 2001/0iF3c/31E-ibP78T05694A000300010025-8
UTM
Coordinates
HAMHUNG #1 (S-9) CV739196
Transformer yard and control house
destroyed; transformer and controls
25X1B installed revetments
25X1B
25X1B
HAMHUNG #2 (S-10) CV761166
Transformer yard and control house
destroyed; 6 transformers in covered
revetments along dike
HONGWON (S-11) DV101316
Transformer yard and control house
destroyed; transformer and control
equipment in nearby revetments
HUNGNAM #1 (3-12) C1780115
Transformer yard destroyed; control
house damaged; several transformers
revetted nearby; control houSe
undergoing repairs
HUNGNAM #2 (5-13) CV795111
Transformer yard and control house
destroyed:
HUNGNAM #3 (S.14) CV824105
Transformer yard and control house damaged
HUNGNAM #4 (S-15) CV832102
Transformer yard and control house badly
damaged and abandoned
HUNGNAM. #5 (S-16) 0V792082
Transformer yard and control house badly
damaged and abandoned
Approved For Release 2001/08/13 : e1A-RDP78T05694A000300010025-8
SECRET
25X1D
25X1B
25X1B
Approved For Release 2001/06E3CRIEEP78T05694A000300010025-8
HUNGNAM #6 (3-17)
Transformer yard and control house destroyed
HUNGNAM #7 (8-18)
Transformer yard and
control
house located
UTM
Coordinates
CV800080
CV820112
HUNGNAM #8 (S-19) CV798113
Transformers ard controls
25X113
KIGOK (3-20) CV771339
Transformer yard and control house
damaged; equipment moved to 6 or more
nearby revetments-
NAJIN (8-21) FB063772
Station intact
OCHONJANG #1 (s-22) DA846294
Slight damage; equipment moved into
7 nearby revetments
OCHONJANG #2 (8-23) (MINE) DA805289
No damage
PYONGYANG (S-24) YD3922
Sub-station totally destroyed
SAGU (S-25) BU779049
Transformer yard abandoned; control
house intact; 6 transformers revetted
Approved For Release 2001/08/13 : eIA-RDP78T05694A000300010025-8
SECRET
25X1D
25X1D
25X1B
Approved For Release 2001/08SIECTP78T05694A000300010025-8
UTM
Coordinates
TANCHON (3-26) DV896786
Transformer yard abandoned; 2 of 3
control buildings damaged; 5 trans-
formers revetted and camouflaged; control
equipment found in 3 buildings on hirside
UMPO (S-27) DV225334
No damage; transformers and control
equipment revetted
WONSAN #1 (S-28)
Transformer yard and control yard
25X1B destroyed;
25X1B
WONSAN #2 (5-29)
Transformer yard and control house
destroyed
YANGJI-DONG (5-30)
Transformer yard and control house
damaged
YATAE-RI (S-31)
Transformer yard and control house
damaged; 2 transformers and control
equipment in 2 concrete revetments
Approved For Release 2001/08/13 : h1A-RDP78T05694A000300010025-8
SECRET
cv624345
cv689315
cv586400
cv585475
25X1D
Approved For Release 2001/08/13 : CIA-RDP78T05694A000300010025-8
NORTH KOREA
Electric Power Installation
Damage Assessment Report
? hydroelectric Power Plant
? Hiernial-electric Power. Plait
A Flectric Switching Station
Statute Moles
0 25 50 /5
SECRET Kilometers
_
7,5
SECRET
glii.11.1111111191.11.011MMIMMIMM1101.10111?101111.0MINMI
?4-3
enydng
M""n N
S 21
'apn dons
011,15.11
pdong
Susdng
Nanam
Porydn
? 42
ang,"
S 7
yongsong s 4
I_SS 6 3
S 5
yesanDn
raernun dong
Yonglda n-dong
Kanggye
?Myongch on
T2
KrIchu
Obak tong
M m'yOng
SIndae
.
S 26
Hongwon
59
S10
Sukch'On
Sorra
S 2
Ky
Chinnamp'o
Ill an
Chadgyon
H
36
N,
IRS
e'lwarrgju
Saldl
i
SOngch'On
Anbybn
H 11
S25 oKoksan ,....7
/-1 \Y --a
)/ Sep'od
dVangdo
Pokkye-rl
'.-? p' yOng 5 a ng
Ch oroerSn ....--
Kamch'On
S 12
S 13
S 14
S 15
S 16
S 17
S 18
S 19
ongch1 ton
DEMARCATION LINE
27 July 1953
Yangyang
SEA
OF
JAPAN
40-
39
MOnSan
ChnnchO1
Y E I:LOW SEA
Samch'dk
dm II
Togye
-(d1/
SECRET
Approved For Release 2001/08/13 : CIA-RDP78T05694A000300010025-8
130
Approved For Release 2001/06'E_ WDP78T05694A000300010025-8
COME tuttl
Approved For Release 2001/08/13 : CIA-RDP78T05694A000300010025-8