NPBO PRE-BUY CONDENSER PUMPS AND CHILLER SPECIFICATION REVIEW

Document Type: 
Collection: 
Document Number (FOIA) /ESDN (CREST): 
CIA-RDP89-00244R000300150003-5
Release Decision: 
RIPPUB
Original Classification: 
K
Document Page Count: 
9
Document Creation Date: 
December 22, 2016
Document Release Date: 
April 2, 2009
Sequence Number: 
3
Case Number: 
Publication Date: 
November 4, 1983
Content Type: 
REPORT
File: 
AttachmentSize
PDF icon CIA-RDP89-00244R000300150003-5.pdf395.48 KB
Body: 
Approved For Release 2009/04/02 : CIA-RDP89-00244R000300150003-5 S NPBO Pre-Buy Condenser Pumps and Chiller Specification Review a) The specification requires 4160 volt condenser water pump motors. Since two of the existing condenser water pumps are 480 volt, is this indicative of the fact all new electrical switchgear will be for 4160 volt motors? b) Chilled water pump specifications were not provided. However, if new chilled water pumps are purchased, they should have mechanical seals to preclude unnecessary water make-up to a closed system. c) Does the specification insure the most energy efficient chiller on the market will be obtained? d) Once these items are purchased, will they be stored (and where) or will they be installed in the Power Plant? If these units are to be installed, will this be accomplished under the new building contract? e) Does the chilled water temperature differential of 580F to 42oF include the existing building requirements? Is the 420F leaving temperature requirement based on new or existing building requirements or would a higher temperature (say 45?F) be acceptable. f) It is recommended that the GSA operating engineer technicians be allowed to review and comment on these specifications since they have "hands-on" experience with this type of equipment. Approved For Release 2009/04/02 CIA-RDP89-00244R000300150003-5 Approved For Release 2009/04/02 : CIA-RDP89-00244R000300150003-5 SH&G 1315 BP-3SC SECTION 15600 PAGE 1 ? CENTRAL INTEWGENCE AGENCY DATE 10/21183 TIME 17.526 HEADQUARTERS EXPANSION CHILLERS BID PACKAGE 3SC SUPPLY CONTRACT - CHILLERS AND PUMPS ARTICLE INDEX 1. CONDENSER WATER PUMPS 2. CENTRAL LIQUID CHILLER REFRIGERATION MACHINES ***END OF INDEX 1 1) 2 2) GENERAL LINE 1 3 3) FURNISH A TOTAL OF SEVEN (7) CONDENSER WATER PUMPS. 3 4) PUMPS SHALL HAVE THE CAPACITIES AND CHARACTERISTICS AS HEREINAFTER 5) SPECIFIED. 3. 6) PUMP NAMEPLATES SHALL CONTAIN THE GPM AND HEAD AT THE SELECTION POINT. 7) SINCE PUMP NAMEPLATE IS TO HE COVERED BY FIXED INSULATION, THE GPM AND 8) HEAD AT THE SELECTION POINT SHALL ALSO BE INCLUDED IN THE MOTOR 9) NAMEPLATE DATA. 3 10) FURNISH CERTIFIED PUMP CHARACTERISTIC CURVES WITH THE PUMPS SHOWING 11) CAPACITIES, HEADS. EFFICIENCIES AND BRAKE HORSEPOWER THRCUGHOUT THE 12) ENTIRE RANGE OF THE PUMPS WHEN OPERATING SINGLY AND THRU THE RANGE OF 13) THE ENTIRE SEVEN PUMPS OPERATING IN PARALLEL. 3 14) PUMPS SHALL BE SELECTED TO PERFORM THE SPECIFIC DUTY FOR WHICH THEY 15). ARE INTENDED. 3 16) THE RATIO OF THE MAXIMUM PUMP IMPELLER DIAMETER TO THE SELECTED PUMP 17) IMPELLER DIAMETER SHALL BE 1.15 OR GREATER. 3 18) PUMPS SHALL 8E CHECKED FOR LUBRICATION, ALLIGNMENT AND OPERATING 19) CONDITIONS BY A FACTORY REPRESENTATIVE AFTER PUMPS HAVE BEEN SET. 20) LEVELLED, GROUTED. CONNECTED TO PIPING, AND SYSTEM FILLED READY TO 21) OPERATE. 3 22) PUMPS SHALL BE SELECTED TO OPERATE WITHIN TWO PERCENTAGE POINTS OF 23) MAXIMUM EFFICIENCY ON THE IMPELLER CURVE SELECTED AND HAVE A MAXIMUM 24) SUCTION VELOCITY OF EIGHT FEET PER SECOND. 3 25) 26) 3 27) 28) 3 29) 30) 31) 3 32) 33) 3 34) 35) NO POINT ON THE HEAD-CAPACITY CURVE SHALL EXCEED THE MOTOR HORSEPOWER SELECTED TO DRIVE THE PUMP. MOTOR HORSEPOWER AT THE SELECTION POINT SHALL NOT EXCEED 95 PERCENT OF THE RATED MOTOR HORSEPOWER. PUMPS SHALL BE DOUBLE SUCTION SPLIT CASE TYPE. MOTOR DRIVEN THRU A FLEXIBLE COUPLING, MOUNTED ON A COMMON ENCLOSED CAST IRON OR STEEL BASE SUITABLE FOR AND WITH ADEQUATE PROVISIONS FOR GROUTING. PUMP CASINGS SHALL BE CLOSE GRAINED CAST IRON SUITABLE FOR 175 LB. WORKING PRESSURE WITH 125 LB. ANSI FLANGES. THE PUMP VOLUTE SHALL BE SUPPLIED WITH PLUGGED VENT.- DRAIN AND GAGE TAPOINGS. 3 36) PUMP SHAFTS 3 37) 3 38) 39) IMPELLERS SHALL BE SHAFT AND DYNAMICALLY BRONZE,. ENCLOSED DOUBLE SUCTION TYPE, KEYED TO BALANCED- FOR QUIET OPERATION. 3 40) PUMPS SHALL BE EQUIPPED WITH PACKED STUFFING BOX CONSTRUCTION WITH A 41) MINIMUM OF 4 'RINGS OF PACKING PLUS A FLUSH RING TO PROVIDE PROPER 42) FLUSH LUBRICATION. PUMPS SHALL BE EQUIPPED WITH SUITABLE DRIP PAN WITH 43) TAPPED CONNECTION AND PIPING TO DRAIN. Approved For Release 2009/04/02 : CIA-RDP89-00244R000300150003-5 Approved For Release 2009/04/02 : CIA-RDP89-00244R000300150003-5 DATE TO/21/L IME 17.526 CHILLERS { SUPPLY 44) PUMPS SHALL EACH HAVE A CAPACITY OF 4450 45) OR 125 FEET WHEN DRIVEN AT 1750 RPM BY A SH&G 13155 BP-3SC CENTRAL INTELLIGENCE AGENCY HEADQUARTERS EXPANSION BID PACKAGE SSC CONTRACT - CHILLERS AND PUMPS GPM AT A TOTAL DYNAMIC HEAD 200 HORSEPOWER MOTOR. 46) PUMPS SHALL BE INGERSOLL-RAND WORTHINGTON; BUFFALO FORGE; AURORA; 47) PEERLESS; WEINMAN, OR AS APPROVED.` 2 ccM4 L )) 48) MOTORS 49) MOTORS SHALL CONFORM TO THE FOLLOWING STANDARDS AND REQUIREMENTS: 50) "AMERICAN STANDARDS FOR ROTATING ELECTRICAL MACHINERY, C50'. 51) AMERICAN NATIONAL STANDARDS INSTITUTE. 52) "AMERICAN STANDARD TERMINAL MARKINGS FOR ELECTRICAL APPARATUS 53) C6.1" AMERICAN NATIONAL STANDARDS INSTITUTE. 54) "NEMA STANDARDS FOR MOTORS AND GENERATORS". LATEST EDITION. 55) "AMERICAN STANDARD DEFINITIONS OF ELECTRICAL TERMS", AMERICAN 56) NATIONAL'STANDARDS INSTITUTE. 57) THE MOTOR HORSEPOWER RATINGS SPECIFIED. SCHEDULED. OR SHOWN SHALL BE 58) UNDERSTOOD TO BE THE MINIMUM ACCEPTABLE AND THE INDICATED MOTOR SPEEDS 59) THE MAXIMUM ACCEPTABLE. MOTORS SHALL BE SUITABLE FOR OPERATION ON 416C VOLT, 3 PHASE. 6b HERTZ ELECTRICAL SERVICE. MOTORS SHALL BE NEMA RATED "U" FRAME. "T" FRAME MO TORS ARE NOT ACCEPTABLE. 64) 65) 66) 3 67) 68) 3 69) 70) 71) 3 72) 73) 3 74) 75) MOTORS SHALL BE GENERAL PURPOSE, SQUIRREL CAGE INDUCTION TYPE, DESIGN *48", ACROSS-THE-LINE FULL VOLTAGE STARTING 1,ITH MAXIMUM SLIP OF 5 PERCENT AND LOCKED ROTOR AND BREAKDOWN TORQUES AS DEFINED IN NEMA. l MOTORS SHALL BE OPEN. DRIP-PROOF NEMA CLASS B INSULATION. RATED 1.15 SERVICE FACTOR. SPEED CLASSIFICATION SHALL BE AS INDICATED OR REQUIRED FOR THE SERVICE AND IN ACCORD WITH THE ESTABLISHED NEMA STANDARDS SECTIONS MG1-1.15 THROUGH MG1-1.20. MOTORS SHALL OPERATE SUCCESSFULLY AT RATED LOAD WITH MAXIMUM VOLTAGE VARIATION OF PLUS OR MINUS 10 PERCENT AT RATED FREQUENCY. MOTORS SHALL BE SIZED SO THAT THEIR DESIGN LOADS SHALL NOT EXCEED 95 PERCENT OF THEIR RATED LOADS. 3 76) MOTORS SHALL HAVE CODE LETTERS FOR LOCKED ROTOR KVA PER HORSEPOWER AS 77) DEFINED IN ACCORD WITH NEMA SECTION MG1-2.14. 3 78) MOTORS SHALL HAVE NAMEPLATES ATTACHED THERETO THAT SHALL GIVE MINIMUM 79) INFORMATION AS DEFINED IN NEMA SECTION MG1-2.15. WHENEVER THE MOTOR 80) NAMEPLATE IS NOT VISIBLE. A PLATE WITH DUPLICATE INFORMATION SHALL BE 81) PROVIDED WHERE IT CAN BE READILY SEEN. NAMEPLATES SHALL NOT BE REMOVED 82) FROM MOTOR. 3 83) MOTOR ACCESSORIES SHALL INCLUDE: 4 84) GREASE LUBRICATED BEARINGS. 4 85) TYPE OF MOUNTING AS REQUIRED WITH STANDARD DIMENSIONS IN ACCORD 86) WITH NEMA SECTION MGT-PART 3. 4 87) JUNCTION BOX OF ADEQUATE SIZE TO TERMINATE THE INDICATED CONDUIT 88)- AND WIRE. SPECIAL BOX EXTENSIONS SHALL BE PROVIDED IF NECESSARY. 89) JUNCTION BOX SrIALL HAVE A SEPARATE LUG FOR GROUND CONNECTION. Approved For Release 2009/04/02 : CIA-RDP89-00244R000300150003-5 Approved For Release 2009/04/02 : CIA-RDP89-00244R000300150003-5 anso uI .-aa. L SECTION 15609 PAGE 3 t CENTRAL INTEL ENCE AGENCY DATE DATE 10/21/83 TIME 17.526 t1f HEADOU AR TER aS PoArNS ION CHILLERS BID PACKAGE 3SC / SUPPLY CONTRACT - CHILLERS AND PUMPS 4 90) SOLDERLESS CONNECTORS USED ON ALL MOTOR LEADS. ' 3 91) MOTOR COMPARTMENTS SHALL BE CLEAN AND DRY AND. ADEQUATELY VENTED 92) DIRECTLY TO THE EXTERIOR. 1 3 93) MOTORS SHALL BE AS MANUFACTURED BY DELCO; LIMA; REULAAD; GENERAL 94) ELECTRIC; ELECTRIC APPARATUS; OR AS APPROVED. 3 95) A LOAD TEST SHALL BE CONDUCTED ON ALL MOTORS AND THE CURRENT READINGS 96) TAKEN. UNDER NO CONDITION SHALL THE LOAD CURRENT EXCEED THE NAMEPLATE 97) RATING OF THE MOTOR. IF THIS CONDITION EXISTS. THE CONTRACTING OFFICER 98). SMALL BE NOTIFIED IMMEDIATELY. 1 99) 2. CENTRAL LIQUID CHILLER REFRIGERATION MACHINES .~ 2 100) FURNISH FIVE (5) CENTRIFUGAL LIQUID CHILLER UNITS. WITH SPECIFIED 101) ACCESSORIES. YORK MODEL HT, CARRIER MODEL CB OR TRANE MODEL CVHE. -it. N~/nPr-? E C C O O NONO MM~? 1U2) FOR OPERATING Y. THE CHILLERS SHALL BE CAPABLE OF STARTING AND 103) OPERATING AT PART LOAD WITH THE ENTERING CONDENSER WATER TEMPERATURE AS 104) LOW AS THE ENTERING CHILLED WATER TEMPERATURE. IF THE CHILLER IS 105) INCAPABLE OF.MEETING THIS REQUIREMENT. THE CHILLER MANUFACTURER SHALL 106) SUPPLY A THREE-WAY COOLING TOWER BYPASS VALVE, WHICH WILL BE INSTALLED BY 107) THE INSTALLING CONTRACTOR. 2 108) EACH UNIT SHALL BE A COMPLETE FACTORY PACKAGE INCLUDING A CENTRIFUGAL 109) COMPRESSOR, OPEN OR HERMETIC MOTOR. COMPRESSOR MOTOR STARTER, COOLER, 110) CONDENSER AND PURGE OR PUMPOUT UNIT. UNIT SHALL BE FACTORY ASSEMBLED, 111) PIPED. WIRED AND LEAK TESTED. IF THE MANUFACTURER DOES NOT PROVIDE A UNIT 112) AS A COMPLETE FACTORY PACKAGE. THE INSTALLING CONTRACTOR WILL FURNISH THE 113) NECESSARY LABOR AND MATERIAL TO COMPLETE THE ASSEMBLY MITH THE 114) SUPERVISION OF THE MANUFACTURER'S REPRESENTATIVE. MANUFACTURER OF CHILLER 115) SHALL HAVE A FACTORY MAINTAINED SERVICE ORGANIZATION AND REPAIR PARTS 116) STOCK WITHIN THE AREA. 117) EVAPORATOR AND CONDENSER SHALL BE OF SHELL AND TUBE TYPE DESIGN IN 118) ACCORDANCE WITH REQUIREMENTS OF THE ASME CODE FOR UNFIRED PRESSURE 119) VESSELS. REFRIGERANT SIDE SHALL BE PROOF-TESTED PER APPLICABLE CODE OR AT 120) 1.5 TIMES MAXIMUM DESIGN WORKING PRESSURE BUT NOT LESS THAN 45 PSIG. A 121) SAFETY RUPTURE DISC IN ACCORDANCE WITH ANSI/ASHRAE 15-1978 SAFETY CODE 122) SHALL BE PROVIDED FOR THE REFRIGERANT CIRCUIT. 123) EACH TUBE SHALL BE INTEGRAL. EXTERNALLY FINNED, 3/4-INCH NOMINAL 124) DIAMETER, SEAMLESS COPPER WITH SMOOTH LANDS AT ALL TUBE SUPPORTS. TUBES 125) SHALL BE INDIVIDUALLY REPLACEABLE WITH TUBE ENDS ROLLED INTO ANNULAR 126) GROOVES IN THE TUBE SHEETS. EACH EVAPORATOR TUBE SHALL BE ROLLED INTO THE 127) INTERMEDIATE SUPPORT SHEETS. . 2 128) WATER BOXES SHALL BE DESIGNED FOR 150 PSIG MAXIMUM WORKING PRESSURE. 129) WATER SIDE SHALL BE HYDROSTATICALLY TESTED AT 1.5 TIMES WORKING PRESSURE. 130) WATER BOXES SHALL BE THE REMOVABLE. COMPACT TYPE WITH $TUB CUT WATER 131) CONNECTIONS HAVING VICTAULIC GROOVES. CONDENSER WATER BOXES SHALL BE 132) HINGED. TAPS FOR VENTS AND DRAINS SHALL BE PROVIDED. 2 133) EVAPORATOR SHALL HAVE ELIMINATORS INSTALLED ALONG ITS COMPLETE LENGTH 134) ABOVE THE TUBES TO PREVENT LIQUID REFRIGERANT FROM ENTERING THE 135) COMPRESSOR. 2 136) LIQUID REFRIGERANT ENTERING EVAPORATOR SHALL BE DISTRIBUTED UNIFRCMLY THE 137) ENTIRE LENGTH Of SHELL AND WITHOUT DIRECT IMPINGEMENT OF HIGH VELOCITY 138) REFRIGERANT ON TUBES. 2 139) FOR STANDARD WATER SELECTIONS, MINIMUM ALLOWABLE REFRIGERANT TEMPERATURE 140) SHALL BE 32 F. AT THE DESIGN CONDITIONS HEREINAFTER SPECIFIED. Approved For Release 2009/04/02 : CIA-RDP89-00244R000300150003-5 SECTION 15601- PAGE 4 DATE IU/21/8TIME 17.526 0 SH&G 13155 OP-3SC CENTRAL INTELLIGENCE AGENCY HEADQUARTERS EXPANSION BID PACKAGE 3SC SUPPLY CONTRACT - CHILLERS AND PUMPS 2 141) RELIEF DEVICES SHALL BE PROVIDED FOR THE REFRIGERANT SIDE. IN ACCORDANCE 142) WITH ANSI 69.1 SAFETY CODE AND LOCAL CODE. MULTIPLE RELIEF DEVICES SHALL 143) BE BROUGHT TO A COM14ON VENT CONNECTION. 2 144) COMPRESSOR SHALL BE OF THE CENTRIFUGAL TYPE. DIRECT DRIVEN At A MAXIMUM 145) SPEED OF 3600 RPM. 2 146) COMPRESSOR IMPELLERS SHALL BE HIGH STRENGTH ALUMINUM ALLOY, BALANCED BOTH 147) STATICALLY AND DYNAMICALLY. IMPELLER SHALL BE PROOF-TESTED AT LEAST 15 148) PERCENT ABOVE DESIGN OPERATING SPEED. 2 149) COMPRESSOR ASSEMBLY SHALL BE RUN-TESTED AT THE FACTORY. VIBRATION SHALL 150) NOT EXCEED 1.0 MIL AT THE COMPRESSOR HOUSING. 2 151) CAPACITY CONTROL SHALL BE BY VARIABLE INLET GUIDE VANES, CAPABLE OF 152) MODULATING PERFORMANCE FROM 10 PERCENT TO 100 PERCENT RATED UNIT CAPACITY 153) AT DESIGN CONDITIONS. SINGLE-STAGE UNITS. OR TWO-STAGE UNITS WITH INLET 154) VANES IN FRONT OF ONLY ONE STAGE OF COMPRESSION, SHALL ALSO INCLUDE 155) AUTOMATIC HOT GAS BYPASS TO ALLOW OPERATION AT 1C PERCENT LOAD. 2 156) MOTOR SHALL BE 2-POLE, CONTINUOUS DUTY, SQUIRREL CAGE INDUCTION TYPE, AND 157) SHALL HAVE AN OPEN DRIP-PROOF OR HERMETIC DESIGN ENCLOSURE. MOTOR 158) FULL-LOAD AMPERES (FLA) AT DESIGN CONDITIONS SHALL NOT EXCEED MOTOR 159) NAMEPLATE FLA. MOTOR SHALL BE FACTORY MOUNTED AND ALIGNED WITH THE 160) COMPRESSOR.. MOTOR SHALL BE DESIGNED FOR USE WITH THE TYPE STARTER 161) SPECIFIED. 162) A POSITIVE DISPLACEMENT SUBMERGED OIL PUMP SHALL PROVIDE LUBRICATION TO 163) ALL PARTS REQUIRING OIL. PROVISIONS SHALL BE INCLUDED FOR CONTROLLED 164) HEATING OF OIL. HEATER SHALL BE SELECTED TO MAINTAIN OIL AT SUFFICIENT 165) LEVEL TO MINIMIZE AFFINITY FOR REFRIGERANT. THE OIL PUMP SHALL BE 166) SUITABLE FOR OPERATION ON 120-VOLT SINGLE PHASE POWER. THIS POWER SHALL 167) BE SUPPLIED THROUGH THE CONTROL POWER TRANSFORMER. Y/UII.1- 168) A REFRIGERANT OR WATER COOLED OIL COOLER SHALL O( PROVIDED. IF THE OIL 169) COOLER IS WATER COOLED THE INSTALLING CONTRACTOR *FURNISH AND INSTALL 170) NECESSARY AUXILIARY WATER PIPING. VALVES AND CONTROLS TO THE OIL COOLER. 171) COMPLETE LUBRICATION SYSTEM SHALL BE FACTORY INSTALLED AND PIPED. 2 172) METHOD OF SENSING MOTOR WINDING TEMPERATURE OF EACH PHASE SHALL BE 173) PROVIDED. THIS DEVICE SHALL INDEPENDENTLY STOP THE COMPRESSOR MOTOR IF 174) EXCESSIVE TEMPERAUTRE IS SENSED IN ANY OF THE THREE WINDINGS. 2 175) INHERENT LOW VOLTAGE PROTECTION SHALL BE PROVIDED. 2 176) INHERENT SINGLE-PHASE PROTECTION (PHASE FAILURE) SHALL BE PROVIDED. THIS 177) MAY BE THE SAME DEVICE WHICH PROVIDES MOTOR OVERLOAD PROTECTION. IT SHALL 178) STOP THE COMPRESSOR MOTOR IF ANY PHASE EXCEEDS ITS OVERLOAD TRIP SETTING. 2 179) UNITS THAT OPERATE AT SUB-ATMOSPHERIC PRESSURE (R-11. R-113, R-114) SHALL 180) BE PROVIDED WITH A COMPLETE PURGE UNIT, PROVIDING POSITIVE MEANS FOR 181) COLLECTION, RETURN OF REFRIGERANT AND REMOVAL OF NON-CONDENSABLES. A 182) SIGNAL LIGHT ON THE CONTROL CENTER SHALL BE PROVIDED WHICH WILL ALERT THE 183) OPERATOR AT OCCURRENCE OF EXCESSIVE PURGING. INDICATING AN ABNORMAL AIR 184) LEAK INTO THE UNIT. 2 185) PURGE UNIT SHALL BE PROVIDED WITH THE FOLLOWING: 7 186) SIGHT GLASS OIL LEVEL INDICATOR. 7 187) ELECTRICALLY HEATED OIL SEPARATOR. 7 188) SECTIONALIZED DRUM PERMITTING SEPARATION OF NONCONDENSAULE 189) GASES AND WATER FROM DISCHARGE OF COMPRESSOR PURGE. 7 19U) MEANS FOR RETURNING REFRIGERANT TO EVAPORATOR AND FOR 191) DRAWING OFF NONCONDENSABLES.. Approved For Release 2009/04/02 : CIA-RDP89-00244R000300150003-5 Approved For Release 2009/04/02 : CIA-RDP89-00244R000300150003-5 SECTION 15600 - PAGE S- 1 SH&G 1315.5 .BP-35C. . ' .... . DATE 10/21/83 TIME 17.526 E DEUCE AGENCY -- CENTRAL INT HEADQUARTERS EXPANSION CHILLERS 81D PACKAGE 3SC SUPPLY CONTRACT - CHILLERS AND PUMPS 7 192) SOLENOID VALVE TO AUTOMATICALLY ISOLATE PURGE SYSTEM 193) FROM CENRIFUGAL MACHINE WHEN PURGE COMPRESSOR IS NOT 194) IN OPERATION. 7 195) WATER CONNECTIONS TO ALLOW OPERATION OF THE PURGE 196) SYSTEM WHEN CENTRIFUGAL MACHINE 1S NOT IN OPERATION. ... 2 197) UNITS THAT OPERATE AUOVE 15 PSIG (R12. R-22. R-500) SHALL BE PROVIDED 198) WITH A SEPARATE COMPRESSOR OPERATED TRANSFER UNIT AND SEPARATE. STORAGE 199) RECEIVER TO PERMIT REMOVAL AND ISOLATION OF THE FULL REFRIGERANT CHARGE 200) ALLOWING INTERNAL INSPECTION OF THE CONDENSER, EVAPORATOR AND CENTRIGUGAL 201) COMPRESSOR. THE STORAGE RECEIVER SHALL BE ASME CODE CONSTRUCTED AND 202) STAMPED. AND fURNI SHED WITH, ANSI 89.1 SAFETY CODE AND LOCAL CODE. PUMPOUT 203) SYSTEM SHALL BE SUPPLIED AND WARRANTED BY THE CENTRIFUGAL MACHINE 204) MANUFACTURER. IT SHALL BE PRE-PIPED AND PRE-MIRED COMPLETE WITH FUSED 205) DISCONNECT, STARTER AND CONTROLS HOUSED IN A NEMA 1 ENCLOSURE. EACH UNIT 206) SHALL HAVE ITS OWN COMPLETE. PUMP-OUT SYSTEM. THE INSTALLING CONTRACTOR 207) WILL FURNISH AND INSTALL.NECESSARY AUXILIARY WATER PIPING AND VALVES TO 208) TRANSFER UNIT CONDENSER. 2 209) EACH CHILLER SHALL BE EQUIPPED WITH AN ELECTRIC CONTROL PANEL AND INCLUDE 210) THE FOLLOWING. 3 211) THREE-PHASE ELECTRONIC CURRENT LIMITING WITH INDIVIDUAL CURRENT 212) TRANSFORMERS. 4 213) ELECTRONIC CURRENT LIMITER SHALL LIMIT THE MAXIMUM AMPERAGE DRAWN 214) BY THE COMPRESSOR MOTOR BY MONITORING ALL THREE PHASES OF SUPPLY 215) POWER. THE INLET GUIDE VANES SHALL MODULATE IN RESPONSE TO THE 216) MAXIMUM AMPERAGE DRAWN BY ANY ONE OF THE THREE PHASES. 4 217) CONTINUOUS VARIABLE POSITION DEMAND LIMITER SHALL PERMIT MANUAL 218) CONTROL OF POWER DEMAND AT ALL OPERATING POINTS FROM 40 TO 100 219) PERCENT OF FULL LOAD POWER. 3 220) ELECTRONIC CAPACITY CONTROL 4 221). SELF-CONTAINED ELECTRIC TEMPERATURE CONTROL SYSTEM, INCLUDING 222) TEMPERATURE. SENSOR. VANE ACTUATOR AND INTEGRATED CIRCUIT 223) MICROPROCESSOR. 224) PRECISE CONTROL OF DEADBAND RANGE SHALL BE FIELD ADJUSTABLE FROM 225) PLUS OR MINUS 1/4 DEG. F TO PLUS OR MINUS 1-1/2 DEG. F. 226) PRECISE CONTROL OF RATE AT WHICH THE CHILLER IS ALLOWED TO LOAD 227) CRAMP FUNCTION) SHALL BE FIELD ADJUSTABLE FROM TWO TO 45 MINUTES. 4 228) UNIT MICROPROCESSOR SHALL INCLUDE A MANUAL FOUR-POSITION (HOLD. 229) LOAD. UNLOAD OR AUTOMATIC) DIAGNOSTIC SWITCH FOR EASE OF 230) MAINTENANCE. 4 231) INDIVIDUAL LIGHTS SHALL INDICATE WHEN MACHINE IS LOADING. 232) UNLOADING. OR IF AUTOMATIC-CURRENT LIMITING IS OCCURRING. 4 233) LOW REFRIGERANT TEMPERATURE OVERRIDE TO AUTOMATICALLY CLOSE THE 234) GUIDE VANES AND UNLOAD THE COMPRESSOR IF LOW REFRIGERANT 235) TEMPERATURE IS DETECTED. 4 236) A METHOD--TO MAINTAIN CAPACITY INLET GUIDE VANES IN CLOSED POSITION 237) DURING COMPRESSOR START-UP. 4 236) ANTIRECYCLE TIMER TO ENSURE 30-MINUTE INTERVAL BETWEEN SUCCESSIVE 239) COMPRESSOR MOTOR STARTS. 4 240) INDIVIDUAL, FRO-IT ADJUSTABLE GAUGES TC INDICATE CONDENSER, 241) EVAPORATOR, OIL AND PURGE DRUM PRESSURES. GAUGES SHALL BE SCALED IN 242) ENGLIISH AND METRIC UNITS. GAUGES SHALL OE ORIFICED TO PREVENT 243) EXCESSIVE SENSITIVITY AND MOVEMENT OF GAUGE INDICATORS. Approved For Release 2009/04/02 : CIA-RDP89-00244R000300150003-5 Approved For Release 2009/04/02 : CIA-RDP89-00244R000300150003-5 SHBG 13155 BP-35C DATE 10/21 TIME 17.526 CENTRAL INTELLIGENCE AGENCY CHILLERS HEADQUARTERS EXPANSION BID PACKAGE 3SC SUPPLY CONTRACT - CHILLERS AND PUMPS 4 244) CAM TIMER TO PROVIDE OPERATION OF OIL PUMP DURING PRELUDE AND 245) POST-LUBE CYCLES. 4 246) SWITCH TO PERMIT MANUAL OR AUTOMATIC OPERATION OF THE PURGE SYSTEM. 288) THE STARTER PANEL DOOR SHALL BE HINGED AND SHALL BE CAPABLE OF BEING 289) PADLOCKED TO PREVENT ACCESS BY UNAUTHORIZED PERSONNEL. 4 247) SAFETY CONTROLS WIRED IN THE MAIN CONTROL POWER CIRCUIT TO THE 248) STARTER. LOW EVAPORATOR TEMPERATURE, HIGH CONDENSER PRESSURE. HIGH 249) MOTOR TEMPERATURE AND LOW OIL PRESSURE CONTROLS SHALL BE WIRED TO 250) INDEPENDENTLY STOP THE COMPRESSOR MOTOR. ADDITIONALLY, EACH OF 251) THESE CONTROLS SHALL BE WIRED THROUGH A FAULT TRIP INDICATOR TO 252) PROVIDE A DOUBLE BREAK OF ALL SAFETY LOCKOUT SYSTEMS. METHOD TO 253) PROVIDE FIRST-OUT INDICATION OF FAULT SHALL BE PROVIDED. MANUAL 254) RESET OF EACH FAULT TRIP INDICATOR SHALL BE REQUIRED. 4 257) ONE ADDITIONAL SET OF NORMALLY CLOSED CONTACTS (CONVERTIBLE TO 258) NORMALLY,OPEN CONTACTS ON EACH FAULT TRIP INDICATOR) TO ALLOW 259) REMOTE ANNUNCIATION OF EACH OF THE FOLLOWING CONDITIONS: LOW 260) EVAPORATOR TEMPERATURE. HIGH CONDENSER PRESSURE. HIGH MOTOR 261) TEMPERATURE. LOW.OIL PRESSURE AND STARTER FAULT. 4 262) 120-VOLT POWER SUPPLIES INDIVIDUALLY FUSED AND INCLUDING: CONTROL 263) CIRCUIT. OIL PUMP SYSTEM CIRCUIT. OIL HEATER CIRCUIT AND PURGE 264) CIRCUIT. 256) STOP THE COMPRESSOR MOTOR. MANUAL RESET SHALL BE REQUIRED. 4 265) FACTORY INSTALLED CONTROL PANEL LIGHTS TO INDICATE SEQUENTIAL 266) START-UP AND OPERATION OF THE CHILLER, INCLUDING: SAFETIES. 267) SATISFIED. COOLING REQUIRED. RESTART TIME ELAPSED. CHILLED WATER 268) PUMP. CONDENSER DATER PUMP. OIL PUMP AND SYSTEM. PROVIDE ELAPSED 269) TIME METER AND STARTS COUNTER.- 4 270) CAPABILITY OF INTERFACING WITH TYPICAL BUILDING ENERGY MANAGEMENT 271) SYSTEMS (DIRECT CURRENT LOAD SHED SIGNALS) TO REDUCE TOTAL 272) ELECTRICAL DEMAND. 4 273) CAPACITY CONTROL MECHANISM WHICH PROVIDES UNLOADED START-UP AFTER 274) POWER FAILURE. 2 275) EACH UNIT SHALL BE FACTORY ANTI-SWEAT INSULATED WITH FLEXIBLE CLOSED CELL 276) INSULATION. INSULATION SHALL BE APPLIED TO THE COOLER PORTION OF THE 277) SHELL AT MINIMUM THICKNESS 3/4 INCH. THE SAMETYPE INSULATION SHALL BE 278) APPLIED TO COMPRESSOR SUCTION PIPING AND OTHER REFRIGERANT PIPING AS 279) NECESSARY. 2 280) THE UNIT MANUFACTURER SHALL FURNISH THE COMPLETE INITIAL CHARGE OF 281) REFRIGERANT AND LUBRICATING OIL. CHILLED WATER AND CONDENSER WATER FLOW 282) SWITCHES, AND FOUR VIRBATION ISOLATION MOUNTS CONSISTING OF 5/8 INCH 283) STEEL MOUNTING PLATES WITH 1 INCH THICK NEOPRENE ISOLATION PADS. 2 284) REMOTE MOUNTED STARTERS 3 285) COMPRESSOR MOTOR STARTER SHALL BE SUPPLIED BY THE CENTRIFUGAL CHILLER 286) MANUFACTURER. STARTER SHALL BE A 5 KV FULL VOLTAGE TYPE ENCLOSED IN A 287) FREE STANDING NEMA-1 ENCLOSURE. 290) THE AMBIENT TEMPERATURE INSIDE .THE STARTER PANEL SHALL NOT EXCEED 155 291) DEG. F (67 DEG. C) WITH ALL COMPONENTS ENERGIZED AT RATED LOAD 292) CONDITIONS AND 104 DEG. F (40 DEG.. C) AMBIENT OUTSIDE THE STARTER 293) PANEL. TEMPERATURE RISE OF COMPONENTS SHALL BE PER RELATED NEC. NEMA 294) AND UL CODES. - Approved For Release 2009/04/02 CIA-RDP89-00244R000300150003-5 Approved For Release 2009/04/02 : CIA-RDP89-00244R000300150003-5 - 7 CENTRAL 1NTE ENCE AGENCY HEADQUARTERS PANSION BID PACKAGE 3SC SECTION 15600 PAGE 7 DATE 10/21/83 TIME 17.526 CHILLERS 5 310) A FAULT TRIP INDICATOR, "MOTOR OVERLOAD" SHALL BE LOCATED IN 311) THE DOOR OF THE STARTER PANEL ENCLOSURE.. THIS FAULT INDICATOR 312) SHALL BE DISPLAYED IF ANY OF THE ABOVE CONDITIONS ARE SENSED AND 313) SHALL CAUSE THE MACHINE TO BE SHUT DOWN. THIS FAULT SHALL 314) REQUIRE MANUAL RESET. ELECTRONIC DIGITAL TIMING SHALL BE 315) PROVIDED BY THE OVERLOAD SYSTEM FOR REPEATABILITY AND ACCURACY. 4 316) THE ELECTRONIC, THREE-PHASE OVERLOAD SYSTEM SHALL BE FIELD 317) ADJUSTABLE FOR PURPOSES OF COORDINATION WITH OTHER ELECTRICAL 318) PROTECTION DEVICES. 319) TO PREVENT THE INCREASINGLY COMMON RAPID RECLOSURE FEATURE CF UTILITY 320) POWER DISTRIBUTION SYSTEMS FROM ADVERSELY AFFECTING THE MECHANICAL AND 321) POWER DRIVE EQUIPMENT, DISTRIBUTION FAULT PROTECTION SHALL BE 322) PROVIDED. 323) THE DISTRIBUTION FAULT PROTECTION SHALL CONSIST OF THREE-PHASE 324) CURRENT SENSING AND MONITORING THE STATUS OF THE STARTER. IF A 325) DISTRIBUTION FAULT IS DETECTED. THE FAULT TRIP INDICATOR 326) "DISTRIBUTION FAULT" SHALL BE DISPLAYED AND MANUAL RESET SHALL BE 327) REQUIRED. DISTRIBUTION FAULTS OF 1-1/2 ELECTRICAL CYCLES DURATION 328) SHALL BE DETECTED AND THE COMPRESSOR MOTOR SHALL BE DISCONNECTED 329) WITHIN SIX ELECTRICAL CYCLES. 3 330) POWER SUPPLY TERMINALS SHALL BE IDENTIFIED BY PERMANENT MARKERS. THE 331) MAXIMUM TEMPERATURE OF TERMINALS SHALL NOT EXCEED 167 DEG. F (7$ DEG. 332) C) WHEN THE EQUIPMENT IS TESTED IN ACCORDANCE WITH ITS RATING. 3 333) CONTACTORS SHALL. BE UL RECOGNIZED FOR AIR CONDITIONING AND 334) REFRIGERATION (DEFINITE PURPOSE) USE. THEY SHALL BE- RATED IN VOLTAGE. 335) CONTINUOUS RATED LOAD AMPERES (RLA) AND LOCKED ROTOR AMPERES (LRA). 336) THE RATING SHALL EQUAL TO OR GREATER THAN THE REQUIREMENTS SPECIFIED 337) ON THE COMPRESSOR MOTOR NAMEPLATE. 3 338) ALL WIRES. BUS BARS AND FITTINGS SHALL BE COPPER ONLY. EXCEPT THE 339) INTERNAL WIRE OF THE CONTROL TRANSFORMER WHICH MAY BE ALUMINUM IF 34U) COPPER TERMINATION IS PROVIDED. 295) A PERMANENT NAMEPLATE SHALL BE PROVIDED AND MOUNTED ON THE STARTER 296) PANEL. IT SHALL IDENTIFY THE MANUFACTURER, SERIAL OR MODEL NUMBER 29?) IDENTIFYING THE DATE OF MANUFACTURE AND COMPONENT REPLATEMENT PARTS 298) AND ALL CURRENT AND VOLTAGE RATINGS. 299) THE ELECTRONIC OVERLOAD SYSTEM SHALL BE COORDINATED WITH THE 300) COMPRESSOR MOTOR AND FACTORY SET AND LABELED WITH THE COMPRESSOR 301) MOTOR RATED LOAD AMPS (RLA). LOCKED ROTOR AMPS (LRA) AND OVERLOAD 302) TRIP (OLT) SETTINGS. THE ELECTRONIC OVERLOAD SYSTEM SHALL PROVIDE: 5 304) EXCESSIVE LOCKED ROTOR CURRENT PROTECTION. 5 305) EXCESSIVE LOCKED ROTOR TIME PROTECTION. S , 306) CURRENT CONTROL OF TRANSITION FROM START TO RUN CONFIGURATION. 5 307) MAXIMUM CURRENT PROTECTION TO PREVENT THE COMPRESSOR MOTOR FROM 308) EXCEEDING ITS OLT SETTING. 3 341) DISCONNECTING MEANS IN THE FORM OF A NON-LOAD BREAK. HIGH INTERRUPTING 342) CAPACITY, FUSED DISCONNECT SHALL BE PROVIDED. 3 343) A 120-VOLT SINGLE-PHASE POWER SUPPLY SHALL BE DEVELOPED WITHIN THE 344)' THREE-PHASE COMPRESSOR MOTOR STARTER AND SHALL BE IN ACCORDANCE WITH 345) - THE CHILLER MANUFACTURER'S SPECIFICATIONS. Approved For Release 2009/04/02 : CIA-RDP89-00244R000300150003-5 Approved For Release 2009/04/02 : CIA-RDP89-00244R000300150003-5 SECTION 156C PAGE 8 SH&G 13155 BP-3SC DATE 113/21/ TIME 17.526 CENTRAL INTELLIGENCE AGENCY CHILLERS HEADQUARTERS EXPANSION BID PACKAGE 3SC SUPPLY CONTRACT - CHILLERS AND PUMPS 3 346) THE STARTER SHALL BE EQUIPPED WITH TWO "PILOT" RELAYS TO INITIATE 347) THE MAIN CENTRIFUGAL STARTER SEQUENCE. THESE RELAYS SHALL BE A 348) SELF-MONITORING SAFETY CIRCUIT WHICH SHALL INDICATE IMPROPER OPERATION 349) (SLOW OPERATION, WELDING OF CONTACTS, ETC.) AND SHALL CAUSE THE UNIT 350) TO BE SHUT DOWN AND A FAULT TRIP INDICATOR TO BE DISPLAYED., THE 351) "STARTER CIRCUIT FAULT" INDICATOR SHALL BE LOCATED IN THE DOOR OF 352) THE ENCLOSURE AND SHALL REQUIRE MANUFAL RESET. 353) A LOCKOUT TRANSITION) SAFETY CIRCUIT SHALL BE PROVIDED TO PREVENT 354) DAMAGE FROM PROLONGED ENERGIZATION DUE TO MALFUNCTION OF THE 355) . TRANSITION CONTACTOR. MALFUNCTION SHALL CAUSE THE MACHINE TO Be SHUT 356) DOWN AND THE "STARTER CIRCUIT FAULT" INDICATOR TO BE DISPLAYED. 357) THE ELECTRONIC. THREE-PHASE OVERLOAD SYSTEM SHALL PROVIDE PROTECTION 358) TO THE COMPRESSOR MOTOR. 359) THE OVERLOAD SYSTEM SHALL BE COORDINATED WITH THE CURRENT CONTROL 360) SYSTEM TO PROVIDE FAIL-SAFE CIRCUITRY. A SINGLE ADJUSTMENT SHALL BE 361) USED TO SET ALL THREE OVERLOADS AND THE CURRENT CONTROL SIGNAL. ALL 362) THREE PHASES SHALL BE MONITORED AND THE HIGHEST OUTPUT SHALL BE 363) USED IN THE OVERLOAD AND CURRENT CONTROL SYSTEMS. 364) TERMINAL CONNECTION PADS SHALL BE PROVIDED TO WHICH CUSTOMER APPLIED 365) LUGS CAN BE ATTACHED. PROVIDE SUFFICIENT SPACE FOR STRESS CONE 366) TERMINATION. 3 367) i 3 ? 368) PROVIDE GROUND FAULT PROTECTION. A CIRCUIT BREAKER SHALL TRIP WHEN THE 369) DIELECTRIC RESISTANCE IS SIGNIFICANTLY REDUCED IN EITHER THE STARTER I 370) OR COMPRESSOR MOTOR. INDICATION AND RESET SHALL BE LOCATED IN THE 371) STARTER DOOR. 2 372) CAPACITY 3 373) EACH UNIT SHALL HAVE A CAPACITY OF 1600 TONS OF REFRIGERATION, f 374) DELIVERING 2400 GPM OF CHILLED WATER COOLED FROM 58 DEG F. TO 42 DEG 375) F. WHEN SUPPLIED WITH 4800 GPM OF CONDENSER WATER AT 85 DEG F. WITH A 376) 10 DEG F. TEMPERATURE RISE. 13 13 378) THREE-PASS CHILLER PRESSURE DROP' SHALL NOT EXCEED 43 FT. OF WATER AND 379) TWO-PASS CONDENSER PRESSURE DROP SHALL NOT EXCEED 25 FT. OF WATER. ~KVV ON 380) COMPRESSOR MOTOR OPERATING Kai 4160 VOLTS SHALL RA`)Y BE A MAXIMUM OF 381) 1109. WITH A MAXIMUM MOTOR DESIGN KW OF 1180., DESIGN RLA SHALL BE 184 382) AND LRA 925. 384) EACH CHILLER SHALL BE PRE-ASSEMBLED AT THE FACTORY AND THE COMPRESSOR 385) SHALL BE GIVEN A RUN-IN-TEST ON AIR. THE ENTIRE JNIT SHALL BE LEAK 386) TESTED, COMPONENTS MATCH MARKED AND THEN DISASSEMBLED FOR SHIPMENT. 387) COMPONENTS FOR FIELD ASSET-0BLY SHALL HAVE GASKETED AND BOLTED FLANGED 388) CONNECTIONS. FIELD WELDED CONNECTIONS WILL NOT BE PERMITTED. 390) MANUFACTURER SHALL FURNISH A FACTORY-TRAINED SERVICE ENGINEER WITHOUT 391) ADDITIONAL CHARGE. REPRESENTATIVE SHALL SUPERVISE LEAK TESTING. 392) EVACUATION AND DEHYDRATION USING A HIGH VACUUM PUMP FURNISHED dY THE 393) MANUFACTURER. CHARGING THE UNIT, START-UP AND INSTRUCTION OF 394) GOVERNMENT'S PERSONNEL ON OPERATION AND MAINTENANCE. MANUFACTURER 395) SHALL PROVIDE OPERATING INSTRUCTIONS AND PARTS LIST. REFER TO SPECIAL 396) CONDITIONS.